Purpose of Article: Provide visual reference to wiring Bullhorn RM510C and RM510S units on a rectifier. This diagram is not for the RM520 or the RM540. For those units, see the articles "Bullhorn RM520: Install on a Test Station and Wiring Diagram" and "Bullhorn RM540: Install on a Test Station and Wiring Diagram".
Note: Image file is also attached below to download and see diagram in a bigger resolution.
What this diagram shows
How a Bullhorn RM5 RMU connects to a rectifier, using the RM5 I/O 4 module, the RM5 power supply and the REL2510 relay.
| Connection | From | To |
|---|---|---|
| Power in (10 V to 30 V AC) | Rectifier taps | RM5 power supply Input (10 to 42 V AC, 3 A max) |
| RMU Power (12 V DC) | RM5 power supply Output (12 V, 1 A max) | I/O 4 DC Input (10 to 14 V, 1.5 A max) |
| CH1: Rectifier Amps | Rectifier | I/O 4 analog input CH1 |
| CH2: Rectifier Volts | Rectifier Positive and Negative output terminals | I/O 4 analog input CH2 |
| Relay Control | Relay Ctrl connector on the RM5 I/O 4 module | REL2510 relay control wires |
| M8 Cable | I/O 4 Dome port | RM5 unit |
Relay control wires: land the relay's control wires on the Relay Ctrl connector of the RM5 I/O 4 module. The relay is only needed when the unit interrupts.
Limits printed on the I/O 4: analog inputs 150 V DC max (CAT II). Digital inputs 24 V max.
Caution: do not draw power from taps controlled by the relay. The rectifier cabinet carries high voltage.