Purpose of Article: Provide visual reference to wiring Bullhorn RM510C and RM510S units on a rectifier. This diagram is not for the RM520 or the RM540. For those units, see the articles "Bullhorn RM520: Install on a Test Station and Wiring Diagram" and "Bullhorn RM540: Install on a Test Station and Wiring Diagram".
Note: Image file is also attached below to download and see diagram in a bigger resolution.

RM5 Overview Diagram.png

 

What this diagram shows

How a Bullhorn RM5 RMU connects to a rectifier, using the RM5 I/O 4 module, the RM5 power supply and the REL2510 relay.

Connection From To
Power in (10 V to 30 V AC) Rectifier taps RM5 power supply Input (10 to 42 V AC, 3 A max)
RMU Power (12 V DC) RM5 power supply Output (12 V, 1 A max) I/O 4 DC Input (10 to 14 V, 1.5 A max)
CH1: Rectifier Amps Rectifier I/O 4 analog input CH1
CH2: Rectifier Volts Rectifier Positive and Negative output terminals I/O 4 analog input CH2
Relay Control Relay Ctrl connector on the RM5 I/O 4 module REL2510 relay control wires
M8 Cable I/O 4 Dome port RM5 unit

Relay control wires: land the relay's control wires on the Relay Ctrl connector of the RM5 I/O 4 module. The relay is only needed when the unit interrupts.

Limits printed on the I/O 4: analog inputs 150 V DC max (CAT II). Digital inputs 24 V max.

Caution: do not draw power from taps controlled by the relay. The rectifier cabinet carries high voltage.

Any questions on wiring, submit technical support ticket via https://www.aiworldwide.com/contact-support/