1. From the All Units page, click the Interruption button, check the boxes next to the units that you would like to send the settings to, and select the CP Off setting.
2. When you are ready, click Send and after you confirm the submission you will be redirected to the Interruption page.
3. Click the update button to track your outgoing pack progress.
4. When the send process is complete, the status should look like the example below.
Notes:
- While CP Off is on, Bullhorn Web shows the unit status Cathodic Protection Off. Some satellite units show it after their next data packet. To confirm that CP Off is on, send a Read on Demand (ROD) command to the unit. Amps at zero or close to zero means CP Off is on.
- To turn off CP Off (to go back to a normal state of operation with current flowing to the structure), you must send the interruption settings Interruption Off in the same manner that you sent CP Off. The Stop Interruption COMMAND will NOT cancel the CP Off settings.
- To confirm that CP Off is cleared, send a Read on Demand after the unit takes the Interruption Off setting. Amps should be back at the normal output. If Amps is still close to zero, CP Off is still on.
- CP Off is not the way to turn a rectifier off for maintenance. For maintenance on a rectifier, the technician must physically lock out and tag the main breaker.