Use this article when you service or install an older Bullhorn RM4011, RM4015 or RM4020. It covers site checks, mounting and the unit ground.
Applies to: Bullhorn RM4011, RM4015 and RM4020.
Site checks for all three models
- Leave enough room to open the enclosure easily. The enclosure must be opened to configure the unit.
- The antenna or satellite terminal location must be clear of obstructions such as buildings, trees and hills.
- It must have a clear line of sight facing the sky to the south.
- It must be at least 2 feet above the solar panel, to prevent signal interference during data transmissions.
- Use only accessories that meet American Innovations specifications.
Mount an RM4011 or RM4015
The unit can be mounted inside or outside the rectifier case with the optional mounting brackets.
- Use a Phillips head screwdriver to attach one of the four plastic brackets from the accessory kit to each corner of the enclosure.
- Hold the enclosure against the flat surface where you will mount it, and mark the bracket hole locations.
- Set the enclosure aside and drill the four holes with a bit that suits the surface (metal, masonry or wood).
- Secure the unit to the mounting surface.
Mount an RM4020
- Mount the enclosure in a clear, unobstructed area with enough working space to open it for maintenance and configuration. Mounting hardware is included with the enclosure.
- Install the antenna at least 2 feet above the solar panel.
Ground an RM4020
- Attach the ground wire to the ground connection screw on the unit.
- Connect the other end of the ground wire to the rectifier frame with spade connectors.
- If needed, use an I-beam clamp to secure the spade connectors. Remove any paint where the clamp attaches to the frame.
RM4020 input channels
- Channels 1, 3 and 4: analog, plus or minus 5 V DC.
- Channel 2: analog, plus or minus 100 V DC.
- Channels 5 and 6: digital. Channel 5 can also be used as an accumulator.
Note: because installation and grounding methods vary, American Innovations cannot warranty damage to equipment caused by lightning strikes.
For any wiring questions, submit a technical support ticket at https://www.aiworldwide.com/contact-support/.