(AI KB) Bullhorn RM510, RM520 and RM540: Readings Look Wrong or Are Missing

Use these checks when a reading in Bullhorn Web looks wrong, or a channel shows no reading.

Applies to: RM510C, RM510S, RM520C, RM520S, RM540C, RM540S

Steps:

  1. Check that every wire is connected securely at both ends.
  2. Measure with a voltmeter at both ends of the wires. The two readings should match.
  3. Check for greater than 20V AC on the DC inputs, this can skew readings.
  4. Check that the shielding on the wires has not been nicked or damaged.
  5. Check that each wire is on the correct channel:
    • On the RM510, the purple wires default to the amps channel, while yellow is volts.  
    • On the RM520 and RM540 harness, Black goes to Pipe 1 and White goes to Pipe 2.
  6. Check polarity: The solid-colored wire is (+), the striped color/white wire is (-).
  7. Check that the unit is grounded to the same ground as the rectifier.
  8. Check that the channel scaling is correct on FieldPro or Bullhorn Web comparing it to your voltmeter.

Good to know:

  • If the FieldPro reading matches your voltmeter but Bullhorn Web is different, the problem is in the channel settings or antenna cable, not the wiring.

Please follow your company's safety checklist when you work on this equipment.

When to contact support:

If the readings are still wrong after these checks, submit a support request. Include the unit serial number, the channel, the reading in Bullhorn Web, and your voltmeter reading.