Use these checks when an RM4014 or RM4015 shows wrong readings or does not interrupt the rectifier. These units connect to a PC with a USB cable and use Bullhorn Tools.
Applies to: RM4014, RM4015
Steps (Wrong Readings):
- Check that every wire is connected securely at both ends.
- Measure with a voltmeter at both ends of the wires. The two readings should match.
- Check for greater than 20V AC on the DC inputs, this can skew readings.
- Check that the shielding on the wires has not been nicked or damaged
- Check that each wire is on the correct channel:
- CH1: Amps (±5 V DC)
- CH2: Volts (±100 V DC)
- CH3/4: Analog Reads (±5 V DC)
- Check polarity: positive to positive and negative to negative.
- Check that the unit is grounded to the same ground as the rectifier.
- Check that the channel scaling is correct on Bullhorn Tools PC or Bullhorn Web comparing it to your voltmeter.
Steps (Interruption Fail):
- Measure the DC input on the unit. It should read 12 to 14 VDC. Ensure the correct polarity between the Power Supply and DC Input. With no power here, the unit treats the rectifier as being in AC fail.
- Check that the unit has a GPS lock on Bullhorn Tools PC or Bullhorn Web.
- Check that the relay is wired to the rectifier correctly
- Remove Bus Bar from the rectifier on the portion that is being interrupted and interruption cables not overlapping any power supply.
- Connect the control wire to the switch out connector of the remote monitoring unit
- This wire should read 12V DC when the relay is opened and around 0V DC when closed.
- Relay Troubleshooting:
- If using an REL2510:
- Check that it has 7 to 30 VAC or VDC on Ext Power.
- Check that the rectifier output is within the relay's limits: 100 volts and 100 amps maximum (70 RMS).
- If using a Mercury relay:
- Check that it is mounted upright and that the full cycle is 5 seconds or longer.
- If using a AC Crydom relay:
- Check for at least 24 volts on the taps that are being interrupted.
- If using a DC Crydom relay:
- Check the polarity of the welding cables and that V Power has 8 to 20 VAC or 7 to 30 VDC.
- If using an REL2510:
Good to know:
- The RM4014 and RM4015 run on a 12V, 3.4AH, Rechargeable PS-1230 battery (Part Number: 370042-000)
Please follow your company's safety checklist when you work on this equipment.
When to contact support:
If the problem remains after these checks, submit a support request. Include the unit serial number and what you measured on the switch out