Use this article when an RM4210 or RM4250 sent an over-current alarm, or when the AC or DC current density reading looks wrong or is missing.
Steps (Reset Over-Current Alarm):
- Fix the cause of the over-current first.
- Connect to the unit with the Bullhorn FieldPro app over Bluetooth.
- On the main unit configuration screen, tap Reset Over-Current. This resets the test coupon relay.
- Select Action and Send a Test Message to update the Over-Current status once reset or wait for the unit to call in on its set cycle.
- If the alarm comes back, contact support.
Steps (Incorrect Current Density):
- Connect to the unit with the Bullhorn FieldPro app over Bluetooth.
- Open the Settings screen.
- Tap Modify Settings at the bottom of the screen.
- Check the Coupon Size value for the Test Coupon or Triton Coupon. It must match the coupon installed at the site.
- in² or cm². The wrong coupon size makes the density reading incorrect.
- If you use plan to utilize the alarm, turn on the alarm toggle and check the Alarm Value.
- Check the Input Max (Volts) and Transducer (Amps) value towards the bottom of the settings to ensure the AC Drain Current reading is accurate.
- Enable AC Drain in under the readings page and apply either Schedule 1 or Schedule 2 to retrieve the AC Drain data.
- Tap Update.
Good to know:
- The over-current reset only clears the relay state. It does not change the limit.
Please follow your company's safety checklist when you work on this equipment.
When to contact support:
- You want to change the over-current limit.
- The over-current alarm returns after a reset.
- A current density reading is still missing or wrong after the coupon settings are correct.