(AI KB) Bullhorn RM4210 and RM4250: Over-Current Alarm and Current Density Readings

Use this article when an RM4210 or RM4250 sent an over-current alarm, or when the AC or DC current density reading looks wrong or is missing.

Steps (Reset Over-Current Alarm):

  1. Fix the cause of the over-current first.
  2. Connect to the unit with the Bullhorn FieldPro app over Bluetooth.
  3. On the main unit configuration screen, tap Reset Over-Current. This resets the test coupon relay.
  4. Select Action and Send a Test Message to update the Over-Current status once reset or wait for the unit to call in on its set cycle.
  5. If the alarm comes back, contact support.

Steps (Incorrect Current Density):

  1. Connect to the unit with the Bullhorn FieldPro app over Bluetooth.
  2. Open the Settings screen.
  3. Tap Modify Settings at the bottom of the screen.
  4. Check the Coupon Size value for the Test Coupon or Triton Coupon. It must match the coupon installed at the site.
    • in² or cm². The wrong coupon size makes the density reading incorrect.
  5. If you use plan to utilize the alarm, turn on the alarm toggle and check the Alarm Value.
  6. Check the Input Max (Volts) and Transducer (Amps) value towards the bottom of the settings to ensure the AC Drain Current reading is accurate.
    • Enable AC Drain in under the readings page and apply either Schedule 1 or Schedule 2 to retrieve the AC Drain data.
  7. Tap Update.

Good to know:

  • The over-current reset only clears the relay state. It does not change the limit.

Please follow your company's safety checklist when you work on this equipment.

When to contact support:

  • You want to change the over-current limit.
  • The over-current alarm returns after a reset.
  • A current density reading is still missing or wrong after the coupon settings are correct.