How to set a high or low alarm on an RM510C or RM510S, get notified in Bullhorn Web, and check the backup battery.
Low or High Channel Alarm:
By Default, Channel 1 is rectifier current (Amps). Channel 2 is rectifier voltage (Volts).
- Bullhorn FieldPro:
- Connect to the unit in Bullhorn FieldPro over Bluetooth.
- On the info screen, open the Options menu.
- Open the Settings menu.
- Tap the name of the channel you want to create an alarm for.
- Under DC Alarm Settings, enter the low and high thresholds.
- Set Alarm Persistence. This is how many minutes a reading must stay past the threshold before the unit sends an alarm.
- Tap Update to save.
- Bullhorn Web:
- Select the unit on Bullhorn Web.
- Click on settings.
- Select the [+] Next to the dot and unit name to expand options and select channel settings.
- Click the channel you're wanting to adjust
- Scroll to the bottom and enable either the High Alarm, Low Alarm, or Both.
- Set the Threshold for the alarm
- Select Save
The unit should now have an Outgoing Packet for Settings, once Acknowledged the new alarm will be active.
Alert Notifications (Bullhorn Web):
The unit sends the alarm. Bullhorn Web sends the email or text.
- In Bullhorn Web, select the unit and click Settings.
- On the Unit Info tab, confirm Service Status is "Installed (Notifications ON)". Alerts are not sent for an inactive unit or if notifications are off.
- Click Alerts in the Unit Setup pane.
- Click New Alert and type a name.
- For Type, select Data Alert.
- Rename the alert and add a subject, then click Save. (ensure Enabled is checked)
- Select the alert and click Conditions.
- Click Add Condition.
- Select the data point for the channel you want to be alerted about
- Select the operator:
- Common Overages: Increases, Greater Than, Goes Above, or Changes more than %
- Common Losses: Decreases, Less Than, Goes Below, or Changes less than %
- Add a value when appropriate
- Click Save.
- Select Alert Contacts
- Pick a contact or group from the drop down and press the green (+) to add them
Note: Setting a unit to Goes Above or Below will alert once, Greater than or Less Than will alert for every value in those thresholds.
Power Alarms & Alerts:
- First check: with rectifier power on, the Dome Status LED on the RM5 I/O 4 module should be green.
- A power alarm or alert means the unit lost rectifier power and is running on its backup battery.
- In Bullhorn FieldPro, open the Options menu and tap Readings.
- System bus voltage on the Readings screen:
- 17 to 23 V is Good.
- 15 V is OK but not ideal.
- 14 V is Bad and means it is not recognizing power from the rectifier to the I/O.
- System bus voltage on the Readings screen:
- In Bullhorn Web, RM5 Series Alert Settings can notify you of Power Failure, Battery Status, Interruption Failure and Interruption Verification Alarm.
Backup Battery Charging:
- The backup battery charges on its own whenever the unit has rectifier power.
- To check it, open the Options menu in Bullhorn FieldPro and tap Readings. The Readings screen shows the battery status and voltage.
- A fully charged battery lasts up to two hours after input power is lost, depending on the reporting schedule.
- After power returns, a critically low battery needs 2 to 12 hours of charging before the unit can send again.
- A unit that keeps switching to battery and losing power is losing rectifier power. Check the power supply and wiring before replacing the battery.
Good to know:
- The backup battery is part number 370254-000 (3.6 V, 2.8 Ah lithium-ion, rechargeable).
- When the RM510 detects a power outage, it starts a two-hour timer to resolve. If it doesn't it will switch to a one-way unit to reserve power and transmit on its schedule until dead. It does this until the battery dies. If the power gets restored, it will go back to a two-way device as long as the battery has over 3.6 volts. If the battery is drained below 3.6 VDC then it could take 12 hours to go back to normal.
Make sure you follow your company safety checklist before opening a dome or working at the rectifier.
When to contact support:
- The unit has good rectifier power and still shows a critical battery after 12 hours.
- System bus voltage stays below 14 V with rectifier power on.
- The alarm is set but no notification arrives and Service Status is "Installed (Notifications ON)".