(AI KB) Bullhorn RM510, RM520, RM540: Reporting Schedule, Read on Demand and Commands

Use this article to change how often a unit reports, to ask a unit for a fresh reading, or when a command does not seem to reach the unit.

Steps (Change Reporting):

  1. On Site (Bullhorn FieldPro):
    1. Swipe a magnet on the I/O (RM510) or the outside of the unit, it should begin to flash.
    2. Connect to the unit with the Bullhorn FieldPro App using Bluetooth.
    3. On the Info screen, open the Options menu.
    4. Open the Reporting screen.
      1. In Reporting Mode, pick Off, Repeat or Day of Month. 
        • In Off mode the unit does not report.
        • For Day of Month, pick the days. (Days are limited to the 1st through the 28th)
        • For Repeat, select the Start Date and Set the Reporting Interval, which is how often the unit sends after the start time.
    5. Set the Start Time, which is the time of day the unit sends.
    6. Tap Update.
       
  2. In Office (Bullhorn Web): 
    1. Locate and select the unit in Bullhorn Web.
    2. Click on Settings
    3. Select Reporting
      1. In Reporting Mode, pick Off, Repeat or Day of Month. 
        • In Off mode the unit does not report.
        • For Day of Month, pick the days. (Days are limited to the 1st through the 28th)
        • For Repeat, select the Start Date and Set the Reporting Interval, which is how often the unit sends after the start time.
    4. Set the Start Time, which is the time of day the unit sends.
    5. Tap Save.

Steps (Read on Demand):

  1. Bullhorn FieldPro:
    1. In Bullhorn FieldPro, open the Dashboard. No Bluetooth connection is needed.
    2. Tick the checkbox next to one or more units.
    3. Tap Read on Demand on the action bar and confirm.
    4. Open Activities to follow the command. Status moves from Scheduled to In Progress, then Success or Failed.
    5. Readings update after the command succeeds.
       
  2. Bullhorn Web:
    1. In Bullhorn Web, either select the specific unit or open the All Units page
    2. Click on Commands
      1. In the All Units Page:
        • Check the units you want to apply to command to.
        • Click the Select box.
        • Select Read On Demand.
        • Click Send.

          The units will show if they Acknowledged within the Units > Send Commands Dropdown. You can see the updated reads on your All Units page if your View and filters allow the unit and data columns to be seen.

          Please ensure you close the Schedule Command ribbon on the right side, otherwise any one-way communication units will not show on your All Units Page.
           

      2. On the Individual Unit Page:
        • Select Read On Demand
        • Click Send.

          The unit will show if it Acknowledged the command in the Outgoing Packets tab, and you can see the new read within the Current Data tab.

Steps (Command Not Acknowledged):

  1. Bullhorn FieldPro:
    1. Open Activities and tap the command to see the detail.
    2. If it says Failed, the unit may be offline. Check that the unit has power and signal.
    3. Send the command again once the unit is confirmed to not be experiencing issues as outlined above.
    4. If it still fails, contact support.
       
  2. Bullhorn Web:
    1. Open Outgoing Packets
    2. If it says Failed, the unit may be offline. Check that the unit has power and signal on the Current Data Page.
    3. Send the command again once the unit is confirmed to not be experiencing issues as outlined above.
    4. If it still fails, contact support.

Good to know:

  • Bullhorn Web tries to send an outgoing command to an RM5 satellite unit up to five times. Each try ends after 30 minutes if it does not get through.
  • A satellite unit usually takes 3 to 20 minutes to send a report. It keeps trying until the report is sent.
  • On RM4210, RM4211, RM4250 and RM4251 over Bluetooth, some high-frequency schedules are not offered. Weekly, daily and day-of-month options remain. Use Bullhorn Web for the full list.

Make sure you follow your company safety checklist before working at the unit.

When to contact support:

  • A command fails more than twice while the unit is reporting normally.
  • The unit missed its report date and has power and signal.

Was This Article Helpful?

0 out of 0 found this helpful