Use this article to pick the right current sensor for a Bullhorn RM4210 or RM4250, and to install and set up the optional selectable current transducer.
Applies to: Bullhorn RM4210 and RM4250.
Which sensor for which reading
The RM4210 is built as a coupon test station unit. Its main current reading is current density through a coupon. A shunt reading can also be taken as a secondary reading.
- AC or DC current density: a coupon (Test Coupon or Triton coupon). The limit is 0.2 A.
- Current through a shunt: wire the shunt to PCR+ and PCR-, positive to PCR+ and negative to PCR-. The unit reads it in millivolts.
- AC drain current through a Polarized Cell Replacement (PCR): the optional selectable current transducer, part number 370138-000. Its range can be set to 30, 60 or 120 A.
Steps (install the selectable current transducer)
- Wire the transducer to the two open screw terminals on the unit's 8-pin terminal connector. These are the PCR terminals. Polarity is the same as for the PCR.
- Set the selector switch on the transducer to a range above the highest current of the PCR. Example: for a highest current of 55 A, set the switch to 60.
- Clamp the transducer around the wires that run from the PCR.
- Connect the 8-pin terminal connector to the unit.
- In the Bullhorn Tools Mobile app, open Settings and tap Modify Settings.
- Enter the Input Max (Volts) and the Transducer (Amps) values, then tap Update.
Good to know
- Input Max (Volts) is the highest voltage the transducer puts out. Use the value printed on the transducer. Transducer (Amps) is the current that equals that voltage, for example 60 when the switch is set to 60.
- The reading shows in Bullhorn Web as AC Drain Current. Turn the AC Drain reading on and give it a measurement schedule, or no data comes in.
- The transducer is optional. It goes on a PCR that is already installed.
- Voltage inputs must not exceed 100 V AC or DC.
- For the coupon settings, see the article "Bullhorn RM4210 and RM4250: Over-Current Alarm and Current Density Readings". For wiring by measurement type, see the article "RM4210/RM4211/Triton/Test Coupon Wiring Options".
- The RM42XX series moves from Bullhorn Tools to the Bullhorn FieldPro app in 2027. After that change, use FieldPro for these steps.
Please follow your company's safety checklist when you work on this equipment.
When to contact support
- The AC Drain Current reading is missing or wrong after the settings are correct.
- You are not sure which sensor fits your site.