Use this article to replace the battery in a Bullhorn RM4010, RM4011, RM4014, RM4015 or RM4020.
Applies to: Bullhorn RM4010, RM4011, RM4014, RM4015 and RM4020. These units sit in a latched enclosure and use a 12 volt lead acid battery.
Follow your company safety checklist, and guard against static before you touch the electronics.
Tools
- Phillips screwdriver
- 3/8 inch nut driver
Steps
- On an RM4010, RM4011, RM4014, RM4015 or RM4020, turn off the power that feeds the field wiring.
- Open the enclosure door and turn the unit power switch off.
- Disconnect the input channel wiring.
- Loosen the four Phillips screws that hold the faceplate. Take them out and keep them.
- Lift the faceplate and secure it inside the enclosure. The top flange of the faceplate fits in the top groove inside the enclosure.
- Disconnect the red positive (+) cable and the black negative (-) cable from the battery.
- Use the 3/8 inch nut driver to remove the two standoffs that hold the battery bracket. Keep the standoffs and the bracket.
- Take the old 12 volt lead acid battery out and put the new battery in.
- Secure the new battery with the battery bracket and the two standoffs.
- Reconnect the battery cables. Red goes to positive (+). Black goes to negative (-).
- Put the faceplate back with the four Phillips screws.
- Reconnect the input channel wiring.
- Turn the unit power switch on and close the enclosure door.
- Turn the power to the field wiring back on.
Good to know
- The battery in these units is a 12 volt lead acid battery.
- Keep the four faceplate screws, the two standoffs and the battery bracket. You use them again.
- If the unit does not power on with the new battery, contact support.
- This article is only for the RM4010, RM4011, RM4014, RM4015 and RM4020. For the RM4210, RM4211, RM4250 and RM4251, see the article "Bullhorn RM4210, RM4211, RM4250 and RM4251: Battery Life and Battery Replacement".