(AI KB) Bullhorn RM4150 and RM4151: Not Powering On or Not Communicating

Use these checks when a Bullhorn RM4150, RM4150S, RM4151 or RM4151S will not power on or has stopped reporting to Bullhorn Web.

Applies to: Bullhorn RM4150, RM4150S, RM4151 and RM4151S.

Steps:

  1. Look at the RADIO light on the faceplate. Solid green means the unit has a cellular signal and DC power. If it is solid green, go to step 6: "Send a test message".
  2. Light is blinking or off? Check DC power. A blinking light, red or green, means the unit is not getting DC power. After about 10 minutes without DC power the light turns off. Make sure the power switch is ON. Check the power supply and the wiring at the DC INPUT connector. It should read about 12 V DC.
  3. Check the backup battery. Measure it with a voltmeter. The battery is low at 11.0 V and dead at 10.5 V. Replace a dead battery with a Power Sonic PS-1208, 12 V.
  4. Wait for the light to settle. After power returns, the light blinks for several minutes before it turns solid.
  5. Light is solid red? Fix the signal. Solid red means DC power is good but there is no cellular signal. Check that the GSM antenna cable, the one with the blue ring, is tight on the GSM ANTENNA connector. The antenna belongs on a metal surface on the outside of the rectifier. If the light stays red, replace the antenna, then turn the unit off and on.
  6. Send a test message. Connect a PC to the Mini-USB CONFIG port on the unit and open Bullhorn Tools. Click Action, then Send Message. Select Test and click Send. The PACKET light turns solid yellow while the packet is sent and turns off when it is delivered.
  7. Check Bullhorn Web. Open the unit's Unit Detail page and click the Incoming Packets tab. Look for the Test packet to confirm it was received.

Good to know:

  • The unit makes a clicking sound after the power switch is turned on. This is normal.
  • The unit sends a Startup packet to Bullhorn Web each time it powers on.
  • The backup battery is the only part of these units that can be serviced.
  • You can also check battery status in Bullhorn Tools or in Bullhorn Web.
  • An AC fail alert or a DC power input alert in Bullhorn Web means the unit lost incoming power from the rectifier or the DC power supply.
  • Older RM4150 and RM4151 units were built for a cellular network that has shut down. They need an LTE retrofit to communicate. Contact support to arrange one.
  • If Bullhorn Tools will not connect on your PC, see the article "Bullhorn Tools: PC Connection Troubleshooting".

When to contact support:

Submit a support case if any of these is true:

  • The light stays solid red with good power and a new antenna.
  • The light is solid green, but the test message does not reach Bullhorn Web.
  • The unit only reports after you turn it off and on, or it needs a restart every week.
  • Bullhorn Tools will not connect after you follow the PC connection article.

Have ready: the serial number, the color and behavior of the radio light, the DC input voltage and the battery voltage.

Was This Article Helpful?

0 out of 0 found this helpful